CMS200 Product Manual, Issue 6
www.nexo.com Page 49
6.3.9 Celsius or Fahrenheit (CF)
Display
Description Option to set the controller to Celsius (°C) or Fahrenheit (°F).
Considerations
A global reset sets controllers using Fahrenheit (°F) to Celsius (°C).
Applies to all temperature settings and values.
Range 0 (°C) or 1 (°F)
Global default 0 (°C)
6.3.10 Saving dierential (Sd)
Display
Description
Denes the compressor cut-in temperature, when added to the saving set point (SSP)
temperature, during the Saving mode.
Considerations
If the saving dierential (Sd) is set too low, for example less than 2.0°C, the
compressor may cycle on the minimum compressor rest time (rt).
Range 0.0 to 9.9°C (0 to 18°F)
Global default 3.0°C (5°F)
6.3.11 Saving set point (SSP)
Display
Description Denes the compressor cut-out temperature during the Saving mode.
Considerations Must be set above the set point (SP).
Range -9.9 to 9.9°C (14 to 50°F)
Global default 3.0°C (37°F)