CMS200 Product Manual, Issue 6
www.nexo.com Page 51
6.3.15 Fan cycle on (FCO)
Display
Description Denes the active period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 1 to 30 minutes
Global default 5 minutes
6.3.16 Fan cycle o (FCF)
Display
Description Denes the inactive period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 0 to 30 minutes
Global default 20 minute
6.3.17 Alarm delay (Ad)
Display
Description
Denes the maximum time the cooler door can be open before sounding the alarm
buzzer.
Considerations
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
• Update the self-learning matrix for door activity.
• Manage the evaporator fan for door activity.
• Sound door alarms if the door is left open.
Range 0 to 30 minutes
Global default 0 (disabled)