CMS200 Product Manual, Issue 6
www.nexo.com Page 51
6.3.15 Fan cycle on (FCO)
Display
Description Denes the active period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 1 to 30 minutes
Global default 5 minutes
6.3.16 Fan cycle o (FCF)
Display
Description Denes the inactive period of the evaporator fan while the compressor is switched o.
Considerations Fan cycle is the fan cycle on (FCO) time + the fan cycle o (FCF) time.
Range 0 to 30 minutes
Global default 20 minute
6.3.17 Alarm delay (Ad)
Display
Description
Denes the maximum time the cooler door can be open before sounding the alarm
buzzer.
Considerations
If disabled, the door switch is also disabled - if so the controller does not detect door
openings therefore, it does not:
Update the self-learning matrix for door activity.
Manage the evaporator fan for door activity.
Sound door alarms if the door is left open.
Range 0 to 30 minutes
Global default 0 (disabled)