6.3.18 Buzzer duration (b1)
Display
Description
Denes the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the controller switches o the
compressor for the duration of RT before starting door open ‘limp home’ mode.
Considerations
The controller switches o the compressor after the duration dened by alarm delay
(Ad) + buzzer duration (b1 ).
Range 1 to 254 seconds
Global default 60 seconds
6.3.19 Motion sensor enable (Sn)
Display
Description Enables the input from the motion sensor.
Considerations Must be disabled if a motion sensor is not tted.
Range 0 (disabled) or 1 (enabled)
Global default 1 (enabled)
6.3.20 Display stability (d2)
Display
Description
Denes the rate of change of the displayed temperature.
Limiting the rate of change provides a dampening eect so as not to concern users
should the air temperature rise quickly due to a door opening.
Increasing the value for the display stability (d2) slows the rate of change of the
displayed temperature.
Considerations Use the global default value for normal operation.
Range 1 to 254
Global default 46