CMS200 Product Manual, Issue 6
www.nexo.com Page 57
6.3.27 Buzzer enable (b0)
Display
Description
Enables or disables a warning buzzer for alarm conditions. Door open alarms always
sound the warning buzzer regardless of this parameter setting.
Considerations
The following alarm conditions trigger the buzzer:
Refrigeration system failure (rSF), Sensor failure (PF1, PF2, PF3) and Ht alarms.
Door alarms sound the buzzer as standard.
Range 0 (disabled) or 1 (enabled)
Global default 1 (enabled)
6.3.28 Saving temperature disable (PEr)
Display
Description
Disables the saving mode temperatures so that the controller maintains the
Ready mode temperatures at all times.
Disabling the Saving mode temperatures does not aect the light functionality.
Considerations None
Range 0 (o) or 1 (on)
Global default 0 (o)
6.3.29 Learning period (LP)
Display
Description Denes whether the controller uses a 1-day or a 7-day learning period.
Considerations None
Range 0 (1 day) or 1 (7 days)
Global default 0 (1 day)