6.3.33 Defrost termination method (dtF)
Display
Description
Provides the option to end a defrost cycle as follows:
on the defrost duration (dd) only
on defrost duration (dd) or defrost termination temperature (dtd).
If the defrost termination method (dtF) is set to use the defrost duration (dd) or the
defrost termination temperature (dtd), the EMS controller ends the defrost cycle on
the rst to occur.
Considerations Defrost method (dF) must be set to 0
Range 0 (time[dd]) or 1 (time[dd] or temperature[dtd])
Global default 1 (time or temperature)
6.3.34 Defrost activation temperature (ddt)
Display
Description
Denes the temperature measured on the evaporator sensor that activates an o-
cycle defrost.
The defrost activation temperature minimizes the risk of evaporator icing up.
Considerations
Defrost method (dF) must be set to 1 to start defrost cycles on the defrost
activation temperature.
Range -14 to 5ºC (7 to 41ºF)
Global default -10ºC (14°F)