6.13 Modbus communications: Cannot
communicate using Modbus
®
RTU
Recommended actions
1.
Verify the use of RS-485.
2. Verify wiring connections.
3. Verify if termination or a pull up is required.
a) Verify that Modbus serial communications settings in the Gateway
match the Modbus Host settings.
b) Log on to the Gateway and navigate to SETUP MODBUS
COMMUNICATIONS.
4. Verify the Modbus address for the Gateway.
5. Verify Modbus register mapping in the Gateway.
a) Log on to the Gateway and navigate to SETUP MODBUS MAPPING.
6.14 Modbus communications: Cannot
communicate using Modbus
®
TCP
Possible cause: Incorrect settings
Recommended actions
1.
Verify secure/unsecure Modbus protocol settings in the Gateway.
a) Log on to the Gateway.
b) Navigate to SETUP SECURITY PROTOCOLS.
2. Verify the Modbus TCP communications settings in the Gateway.
a) Log on to the Gateway.
b) Navigate to SETUP MODBUS COMMUNICATIONS.
3. Verify Modbus register mapping in the Gateway.
a) Log on to the Gateway.
b) Navigate to SETUP MODBUS MAPPING.
6.15 Modbus communications: Cannot
communicate using secure Modbus
®
TCP
Reference Manual Troubleshooting
00809-0600-4410 May 2020
Emerson 1410S/781S 49