Prepare discrete input/output cables
AMS 6500 discrete input/output cable pulls are low voltage DC only, so they can be routed
with sensor cables or routed separately. They consist of either multi-pair bundled cable
pulls or single twisted pair cable.
Procedure
1. For multi-pair bundled cable pulls, prepare 1.5 in. conduit for one cable and 0.5 in.
extra for each additional cable.
2. Run single twisted-pair cable in conduit or pull through the enclosure using 0.25 in.
cord grips.
4.3.4 Install and remove modules
The AMS 6500 system cabinet can be configured to contain both prediction and
protection modules. In Figure 4-8, the protection modules (3U high modules) are shown on
the left; the prediction modules (6U high modules) are shown on the right.
AMS 6500 with 3U and 6U high modulesFigure 4-8:
Install or remove 3U high protection module
Install or remove protection monitor cards, relay modules, and communication modules.
Protection modules are hot-swappable and can be installed or removed while the rack is
powered. Refer to the A6500 protection cards manual for instructions.