Terminal descriptors for MSIG 2Table 6-5:
J5 J6 J7 J8
CH13
SIG+13/+24 V
CH17
SIG+17/+24 V
CH21
SIG+21/+24 V
TACH3
Tach+3
SIG-13/+24 V return SIG-17/+24 V return SIG-21/+24 V return Tach-3
-24 V -24 V -24 V -24 V
Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return)
Shield Shield Shield Shield
CH14
SIG+14/+24 V
CH18
SIG+18/+24 V
CH22
SIG+22/+24 V
TACH4
Tach+4
SIG-14/+24 V return SIG-18/+24 V return SIG-22/+24 V return Tach-4
-24 V -24 V -24 V -24 V
Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return)
Shield Shield Shield Shield
CH15
SIG+15/+24 V
CH19
SIG+19/+24 V
CH23
SIG+23/+24 V
I/O3
I/O+3
SIG-15/+24 V return SIG-19/+24 V return SIG-23/+24 V return I/O-3
-24 V -24 V -24 V -24 V
Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return)
Shield Shield Shield Shield
CH16
SIG+16/+24 V
CH20
SIG+20/+24 V
CH24
SIG+24/+24 V
I/O4
I/O+4
SIG-16/+24 V return SIG-20/+24 V return SIG-24/+24 V return I/O-4
-24 V -24 V -24 V -24 V
Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return) Gnd (-24 V return)
Shield Shield Shield Shield
6.4 Signal routing from the monitoring panel to
the prediction panel
You can set DIP switches on the A6500-M-RTRM termination panel to route sensor and
tachometer signals from the A6500-P-RTRM termination panel. Set these switches to the
ON position to connect to their respective A6500-P-RTRM buffered outputs. See
Rear termination panel for DIP switch locations.
The external input connectors on the A6500-M-RTRM are connected to the 12-2-2 module
signal inputs, regardless of whether the DIP switches are set to ON or OFF. Therefore, if a
DIP switch is set to route an input from the A6500-P-RTRM, do not connect an external
sensor to the associated external input of the A6500-M-RTRM. Set the DIP switches for
accelerometer power to OFF while routing inputs from the A6500-P-RTRM.
Wire terminations
MHM-97125-PBF-EN, R0 43