7.3 Configure the A6560R with a terminal
emulator
7.3.1 Configure a serial port connection from a computer
Use a terminal emulator such as Telnet or HyperTerminal to connect to the AMS Machinery
Health Monitor using a serial cable or an Ethernet cable.
(1)
Configure the settings in
Table 7-2 in the terminal emulator's connection settings.
Prerequisites
You need a username and password to log on to a AMS Machinery Health Monitor with
Telnet.
Serial port connection setupTable 7-2:
Setting Value
serial port COM1
baud rate 9600
data bits 8
stop bit 1
parity none
flow control none
7.3.2 Configure A6560R boot parameters with a terminal
emulator
During normal usage, it is unlikely that you will need to change the initial boot parameters.
However, you may need to change boot settings in two situations:
If you replace the processor module. You may replace an A6560 with an A6560R.
The unit is added to an existing Ethernet network that is not directly connected to
the online server through a dedicated cable.
Note
Do not add a unit to an existing network until its processor board IP addresses have been
verified and changed, if necessary, to be compatible with addresses already in use on the
existing network.
Procedure
1. Start a terminal session, and turn the unit on.
(1) Telnet and HyperTerminal are Windows Features that are available but are not enabled by default. You can use other terminal emulator
programs.
Hardware configuration
62 MHM-97125-PBF-EN, R0