6 Wire terminations
Topics covered in this chapter:
Terminate instrumentation wiring
Terminate bundled cable
Wire termination at the AMS 6500
Signal routing from the monitoring panel to the prediction panel
Terminate discrete I/O
Rear shield/Adapter panel—A6500-M-RSH
Terminate +24 V power for the A6560 and A6510 modules
Eddy Current sensor: -24 V power supply
SysFail relay termination
Loop interconnection for 4-20 mA current
Terminate Ethernet connection
Default schema for network addressing
6.1 Terminate instrumentation wiring
Junction boxes have single twisted-pair instrumentation wire pulled through cable grips on
the left side of the box, and one or more bundled 9 twisted-pair cable pulled through a 1.5
in. conduit fitting on the right side of the box. Route cables through the box, leaving a
service loop, and terminate them to 3-lug terminal blocks or industry standard Phoenix
connectors.
Wire terminations
MHM-97125-PBF-EN, R0 33