Junction box routingFigure 6-1:
A. Service loops
B. Permanent cable tie-downs
C. Sensor cables
D. Multi-pair cables
CAUTION!
Use correct gauge strippers on individual conductors. Do not strip more than 0.25 in. off a
conductor. Do not over-tighten. Turn terminal screw clockwise until you make contact with
the wire, then make an additional ¼ turn.
Note
Shield connections pass through junction boxes and are not grounded at the box.
Procedure
1. Starting at the cord grip, pull the wire to the top of the box on the left side. Pull the
service loop as shown in Figure 6-1.
2. Strip one inch of polyurethane jacket from the cable.
3. Carefully pull twisted-pair conductors out of the braided shield without removing
the braided shield.
Wire terminations
34 MHM-97125-PBF-EN, R0