Prepare twisted-pair conductors for terminationFigure 6-2:
Spread braided shield apart and pull the conductors through the separation. Twist the braided
shield together before termination.
4. Strip 0.25 in. from each conductor and twist the end of the braided shield.
5. Terminate the wire into the proper terminal block according to the following:
a. Connect sensor positive input to the upper level of the terminal block.
b. Connect sensor negative input to the middle level of the terminal block.
c. Connect braided shield to the lower level of the terminal block.
Make terminal connections with 24 AWG twisted-pair conductorsFigure 6-3:
A. Wire tag
B. White
C. Black
D. Shield
E. +
F. -
G. Shield
6. Relabel the wire at the phoenix connector.
7. After all cables are terminated, bundle cables and secure against the side of the
junction box using a cable tie down.
Wire terminations
MHM-97125-PBF-EN, R0 35