Introduction and Specifications
September 2013
1-9
Table 1-5. Hazardous Area Classifications—FM (United States)
Certification
Body
Type Certification Obtained Entity Rating Temperature Code
Enclosure
Rating
FM
DVC60x0
DVC60x0S
(x = 1,2,3)
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,
E,F,G per drawing GE42819
Natural Gas Approved
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
T5(Tamb 80C)
T6(Tamb 75C)
Type 4X, IP66
Single Seal Device
XP Explosion-proof
Class I Division 1 GP B,C,D
NI Non-incendive
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
Type 4X, IP66
Single Seal Device
DVC6005
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,E,
F,G per drawing GE42819
Natural Gas Approved
Vmax = 30 VDC
Imax = 226 mA
Ci = 5 nF
Li = 0.55 mH
Pi = 1.4 W
Voc = 9.6 VDC
Isc = 3.5 mA
Ca = 3.6 uF
La = 100 mH
Po = 8.4 mW
T5(Tamb 80C)
T6(Tamb 75C)
Type 4X, IP66
Single Seal Device
XP Explosion-proof
Class I Division 1 GP B,C,D
NI Non-incendive
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
Natural Gas Approved
T5(Tamb 80C)
T6(Tamb 75C)
Type 4X, IP66
Single Seal Device
DVC60x5
(x = 1,2,3)
IS Intrinsically Safe
Class I,II,III Division 1 GP A,B,C,D,
E,F,G per drawing GE42819
Vmax = 30 VDC
Imax = 100 mA
Ci = 0 uF
Li = 0 mH
Pi = 160 mW
T4(Tamb 125C)
T5(Tamb 95C)
T6(Tamb 80C)
Type 4X, IP66
XP Explosion-proof
Class I Division 1 GP A,B,C,D
NI Non-incendive
Class I Division 2 GP A,B,C,D
DIP Dust Ignition-proof
Class II, III Division 1 GP E,F,G
S Suitable for Use
Class II, III Division 2 GP F,G
T4(Tamb 125C)
T5(Tamb 95C)
T6(Tamb 80C)
Type 4X, IP66
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000
CategoryController
LanguageEnglish

Related product manuals