Transducer Block
December 2009
4-51
Table 4-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
Advise Alarm
ADVISE_ALM
58
Data Type: DS-71
Used to report alerts to host
system
UNACKNOWLEDGED 58.1 RW N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined NONE
ALARM_STATE 58.2 RO N/A
0: Undefined
1: Clearreported
2: Clearnot reported
3: Activereported
4: Activenot reported
0=Undefined N/A
TIME_STAMP 58.3 RO N/A 0 N/A
SUBCODE 58.4 RO N/A 0 N/A
VALUE 58.5 RO N/A 0 N/A
Data Type: Float
Value of parameter at alarm time
for single alarm, 0 for multiple
alarms
Failed Active
FAILED_ACTIVE
59 RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0 N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Failed Alert Status
Maintenance Active
MAINT_ACTIVE
60 RO
(1)
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
All bits: 0 N/A
Data Type: Bit String (4 byte)
0=inactive
1=active
Maintenance Alert Status
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
Continued
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals