EasyManuals Logo

Emerson Fisher FIELDVUE DVC6000f User Manual

Emerson Fisher FIELDVUE DVC6000f
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
DVC6000f Digital Valve Controllers
December 2009
4-8
Table 4-2. Parameters Affected by Restart with Defaults
Index
Number
Parameter Name Initial Value
Resource Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5 MODE_BLK
TARGET
PERMITTED
NORMALE
Auto
Auto or Out of Service
Auto
14
18
20
GRANT_DENY
FEATURE_SEL
CYCLE_SEL
All bits: 0
Set by mfgr.
0:0
26
27
28
SHED_RCAS
SHED_ROUT
FAULT_STATE
640000
640000
1=Clear
32
33
34
37
LIM_NOTIFY
CONFIRM_TIME
WRITE_LOCK
ALARM_SUM
DISABLED
MAX_NOTIFY
640000
1=Unlocked
All bits: 0
38
39
ACK_OPTION
WRITE_PRI
Disabled
0
AO Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
9
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT
Out of Service
OOS+MAN+AUTO+CAS+RCAS
Auto
Dynamic
Dynamic
11 PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
100
0
%
2
12
14
15
XD_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
IO_OPTS
STATUS_OPTS
100
0
%
2
All off
All off
17
18
19
20
21
22
CAS_IN
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
CHANNEL
BAD:
NC:
const
0
+INF
+INF
100
0
1=analog valve input
Continued
Table 4-2. Parameters Affected by Restart with Defaults
(Continued)
Index
Number
Parameter Name Initial Value
AO Block (continued)
23
24
26
27
FSTATE_TIME
FSTATE_VAL
RCAS_IN
Status
Value
SHED_OPT
0
0
BAD:
NoComm:
NoVal:
const
0 Trk
All off
PID Block Parameters
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
9
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT
Out of Service
OOS+MAN+AUTO+CAS+
RCAS+ROUT
Auto
Dynamic
Dynamic
10 PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
100
0
%
2
11
13
14
OUT_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
CONTROL_OPTS
STATUS_OPTS
100
0
%
2
0: Bypass enable
All off
15
16
IN
Status
Value
PV_FTIME
BAD:
NC:
const
0
0
17
18
19
20
21
BYPASS
CAS_IN
Status
Value
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
0
BAD:
NC:
const
0
+INF
+INF
100
22
23
24
25
26
27
SP_LO_LIM
GAIN
RESET
BAL_TIME
RATE
BKCAL_IN
Status
Value
0
1
+INF
0
0
BAD:
NC:
const
0
Continued
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals