EasyManuals Logo

Emerson Fisher FIELDVUE DVC6000f User Manual

Emerson Fisher FIELDVUE DVC6000f
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
Resource Block
December 2009
4-11
Table 4-2. Parameters Affected by Restart with Defaults
(Continued)
Index
Number
Parameter Name Initial Value
OS Block (continued)
20
21
BKCAL_2_IN
Status
Value
BAL_TIME
BAD
NC
const
0
0
AI Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
10
MODE_BLK
TARGET
PERMITTED
NORMAL
OUT
XD_SCALE
EU at 100%
EU 0%
Units Index
Decimal point
Out of Service
OOS, MAN, AUTO
Auto
100
0
%
2
11
13
14
15
16
OUT_SCALE
EU 100%
EU 0%
Units Index
Decimal point
I/O OPTS
STATUS OPTS
CHANNEL
L_TYPE
100
0
Trk s/b%
2
disabled
disabled
0
0
17
18
22
23
24
LOW_CUT
PV_FTIME
ALARM_SUM
DISABLED
ACK_OPTION
ALARM_HYS
0
0
0
Disabled
0.5%
25
26
27
28
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM
0
0
0
0
29
30
31
32
37
38
LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
OUT_D
ALM_SEL
0
0
0
0
unselected
MAI Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
7
8
9
10
11
12
13
14
15
MODE_BLK
TARGET
PERMITTED
NORMAL
CHANNEL
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
Out of Service
OOS, MAN, AUTO
Auto
TB.FINAL_VALUE
TB.TRAVEL_TARGET
TB.FINAL_POSITION_VALUE
TB.TRAVEL
TB.SUPPLY_PRESS
TB.ACT_PRESS_A
TB.ACT_PRESS_B
TB.ACT_PRESS_DIFF
Continued
Table 4-2. Parameters Affected by Restart with Defaults
(Continued)
Index
Number
Parameter Name Initial Value
DO Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
5
8
9
MODE_BLK
TARGET
PERMITTED
NORMAL
SP_D
OUT_D
Out of Service
OOS+MAN+AUTO+CAS+
RCAS
AUTO+CAS
11
12
14
15
PV_STATE
XD_STATE
IO_OPTS
STATUS_OPTS
0
0
All off
All off
17
18
19
CAS_IN_D
Status
Value
CHANNEL
FSTATE_TIME
BAD
NC
const
0
22
0
20
22
23
27
28
FSTATE_VAL_D
RCAS_IN_D
Status
Value
SHED_OPT
SP_RATE_UP
SP_RATE_DN
0
BAD
NoComm
NoVal
const
0
All off
0
0
Transducer Block
1
2
3
4
5
87
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
PROTECTION
N/A
NULL
0
1
Out of Service
AUTO, MAN, OOS
Auto
None
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000f and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000f Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000f
CategoryController
LanguageEnglish

Related product manuals