Installation, Operation and Maintenance Manual
VCIOM-01494-EN Rev. 0
June 2022
17
OM1 Module Setting and Conguration
Section 3: OM1 Module Setting and Conguration
Table 1. Setup Optional Card 4 - 20 mA (OM1)
Setup
Rotary Switch Settings Dip Switch Conrm Button
Default
SW9 SW8 SW7 SW4 SW2
Position relay LS3
(AUXC1)
every position 0 0 to 9 ON PUSHED 0%
Position relay LS4
(AUXC2)
every position 1 0 to 9 ON PUSHED 25%
Position relay LS5
(AUXC3)
every position 2 0 to 9 ON PUSHED 75%
Position relay LS6
(AUXC4)
every position 3 0 to 9 ON PUSHED 100%
Set 0% input 4 - 20 mA every position 4 0 ON PUSHED 4 mA
Set 100% input 4 - 20 mA every position 4 1 ON PUSHED 20 mA
Fail-Safe
every position 5 0 (off) ON PUSHED
offevery position 5 1 (fully open) ON PUSHED
every position 5 2 (fully closed) ON PUSHED
Dead band every position 6 0 to 9 ON PUSHED 2.0%
Relays LS3-LS5
every position 7 0: break ON PUSHED
make
every position 7 1: make ON PUSHED
Relays LS4-LS6
every position 8 0: break ON PUSHED
make
every position 8 1: make ON PUSHED
Blinker/Local selector
0 9 0: off ON PUSHED
off
0 9 1: Blinker ON PUSHED
0 9
2: Local
selector
ON PUSHED
Retransmission direct/
reverse
1 9 0: direct ON PUSHED
direct
1 9 1: reverse ON PUSHED
Retransmission volt/mA
1 9 2: mA ON PUSHED
mA
1 9 3: volt ON PUSHED
Set direct/reverse
2 9 0: direct ON PUSHED
direct
2 9 1: reverse ON PUSHED
Position request
3 9 0: off ON PUSHED
off
3 9 1: on ON PUSHED
Set 4 - 20 mA
4 9 0: off ON PUSHED
on
4 9 1: on ON PUSHED
Set 0 - 10 V
5 9 0: off ON PUSHED
off
5 9 1: on ON PUSHED
Offset open
for retransmission
6 9 0: increase ON PUSHED
n.d.
6 9 1: decrease ON PUSHED
Offset closed
for retransmission
7 9 0: increase ON PUSHED
n.d.
7 9 1: decrease ON PUSHED