EasyManua.ls Logo

Emerson Keystone OM1 - EPI2 - Page 21

Emerson Keystone OM1 - EPI2
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, Operation and Maintenance Manual
VCIOM-01494-EN Rev. 0
June 2022
17
OM1 Module Setting and Conguration
Section 3: OM1 Module Setting and Conguration
Table 1. Setup Optional Card 4 - 20 mA (OM1)
Setup
Rotary Switch Settings Dip Switch Conrm Button
Default
SW9 SW8 SW7 SW4 SW2
Position relay LS3
(AUXC1)
every position 0 0 to 9 ON PUSHED 0%
Position relay LS4
(AUXC2)
every position 1 0 to 9 ON PUSHED 25%
Position relay LS5
(AUXC3)
every position 2 0 to 9 ON PUSHED 75%
Position relay LS6
(AUXC4)
every position 3 0 to 9 ON PUSHED 100%
Set 0% input 4 - 20 mA every position 4 0 ON PUSHED 4 mA
Set 100% input 4 - 20 mA every position 4 1 ON PUSHED 20 mA
Fail-Safe
every position 5 0 (off) ON PUSHED
offevery position 5 1 (fully open) ON PUSHED
every position 5 2 (fully closed) ON PUSHED
Dead band every position 6 0 to 9 ON PUSHED 2.0%
Relays LS3-LS5
every position 7 0: break ON PUSHED
make
every position 7 1: make ON PUSHED
Relays LS4-LS6
every position 8 0: break ON PUSHED
make
every position 8 1: make ON PUSHED
Blinker/Local selector
0 9 0: off ON PUSHED
off
0 9 1: Blinker ON PUSHED
0 9
2: Local
selector
ON PUSHED
Retransmission direct/
reverse
1 9 0: direct ON PUSHED
direct
1 9 1: reverse ON PUSHED
Retransmission volt/mA
1 9 2: mA ON PUSHED
mA
1 9 3: volt ON PUSHED
Set direct/reverse
2 9 0: direct ON PUSHED
direct
2 9 1: reverse ON PUSHED
Position request
3 9 0: off ON PUSHED
off
3 9 1: on ON PUSHED
Set 4 - 20 mA
4 9 0: off ON PUSHED
on
4 9 1: on ON PUSHED
Set 0 - 10 V
5 9 0: off ON PUSHED
off
5 9 1: on ON PUSHED
Offset open
for retransmission
6 9 0: increase ON PUSHED
n.d.
6 9 1: decrease ON PUSHED
Offset closed
for retransmission
7 9 0: increase ON PUSHED
n.d.
7 9 1: decrease ON PUSHED

Related product manuals