Installation, Operation and Maintenance Manual
VCIOM-01494-EN Rev. 0
June 2022
19
OM1 Module Setting and Conguration
Section 3: OM1 Module Setting and Conguration
Output 0 - 10 V DC
In order to set output as a 0 - 10 V DC signal, please proceed as follows:
SW1_1 = OFF; SW1_2 = ON; SW1_3 = ON;
SW1_4 = OFF
SW6 = ON
3.1.5 Relays AUXC1, AUXC2, AUXC3 and AUXC4 Settings
The tables below shows reporting the settings of each relays AUXC1, 2, 3 and 4.
Table 2. AUXC1 (LS3)
SW8 SW7 Description
0 0 inactive
0 1 2%
0 2 12.5%
0 3 25%
0 4 37.5%
0 5 50%
0 6 62.5%
0 7 75%
0 8 87.5%
0 9 99%
Table 3. AUXC2 (LS4)
SW8 SW7 Description
1 0 inactive
1 1 2%
1 2 12.5%
1 3 25%
1 4 37.5%
1 5 50%
1 6 62.5%
1 7 75%
1 8 87.5%
1 9 99%
Table 4. AUXC3 (LS5)
SW8 SW7 Description
2 0 inactive
2 1 2%
2 2 12.5%
2 3 25%
2 4 37.5%
2 5 50%
2 6 62.5%
2 7 75%
2 8 87.5%
2 9 99%