Service Menu Parameters
85
Digital Scroll 2 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-
sor to compensate for any error or drift of the sensor.
Calibrated Digital Scroll 2 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Figure 76 Sensor calibration / setup parameters - Page 2
Optional Sensor A, B & C—This parameter adjusts the reading from the actual sensor to compen-
sate for any error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B & C—This parameter shows the adjusted value of the sensor.
This value is the actual sensor reading (+ or -) the offset.
Optional Sensor B &C Type—This parameter currently only supports the “TH” Temperature /
Humidity sensor type.
SENSOR CALIBRATION/SETUP (page 2 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 3) ????
Optional Sensor A 1 +0°F
Calibrated Optional Sensor A 1 72°F
Optional Sensor A 2 +0.0 %
Calibrated Optional Sensor A 2 49.5 %
Optional Sensor B Type TT
Optional Sensor B 1 +0°F
Calibrated Optional Sensor B 1 °F
Optional Sensor B 2 +0.0°F
Calibrated Optional Sensor B 2 °F
Optional Sensor C Type TT
UNIT 01
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622