2-4. Installation for hot standby
If the hot standby function is not used, you may skip this section.
1) Disconnect the jumper wire between the terminals of “BPS” and “L0” on the host UPS.
2) Keep the jumper wire between the terminals of “BPS” and “L0” on the standby UPS.
3) Connect the “L1” of the standby UPS to the “BPS” of the host UPS.
4) Connect the “Output N” of the standby UPS to the “Output N” of the host UPS.
BPS
L0
GND
NOTE: Each UPS must be connected to an independent battery pack.
2-5. Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.