28
6. Specifications
MODEL GXT MT+ LB, 10kVA
CAPACITY* 10000 VA / 8000 W
INPUT
Voltage Range
Low Line Loss
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Comeback Low Line Loss Voltage + 10V
High Line Loss 300 VAC ± 3 %
High Line Comeback High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase Single phase with ground
Power Factor
> 0.99 at 100% Load
OUTPUT
Output voltage 208/220/230/240VAC
AC Voltage Regulation ± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min110%~130%: 1min>130% : 1sec
Battery mode
100%~110%: 30sec110%~130%: 10sec>130% : 1sec
Current Crest Ratio 3:1 max
Harmonic Distortion
3 % @ 100% Linear Load; 6 % @ 100% Non-linear Load
Transfer Time
Line Battery 0 ms
Inverter Bypass 0 ms
EFFICIENCY
AC mode
>
90
%
Battery Mode > 89%
BATTERY
Standard
Model
Type & Numbers 12 V / 9 Ah x 20
Recharge Time 9 hours recover to 90% capacity
Charging Current
Default : 1 A ± 10%
M
ax.
: 2
A ± 10%
Charging Voltage 14.4 V ± 1%
Long-run
Model
Type Depending on applications
Numbers 16 – 20 Derating capacity = original real power capacity x N/20
Charging Current
Default: 4 A ± 10%
Max.: 6A ± 10%
Charging Voltage
14.4
V ± 1%
PHYSICAL
Standard
Model
Dimension,
DXWXH(mm)
442x 190 x 688
Net Weight (kgs) 82
Long-run
Model
Dimension, DXWXH(mm)
442x 190 x 318
Net Weig
ht
(kgs)
2
3
ENVIRONMENT
Operation Temperature
0 ~ 40°C
(battery life cycle will be shorten when temperature is above 25°C)
Operation Humidity <95 % and non-condensing
Operation Altitude** <1000m
Acoustic Noise Level
Less than
58
dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and
MAC
Optional SNMP Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.