EasyManua.ls Logo

Emerson Liebert GXT MT+LB 10KL - Fault Code; Warning Indicator

Emerson Liebert GXT MT+LB 10KL
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
3-8. Fault Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start failure 01 None Battery SCR short circuited 21 None
Bus over 02 None Inverter relay short circuited 24 None
Bus under 03 None Charger output short 2A None
Bus unbalance 04 None Parallel communication
failure
35 None
Inverter soft start failure 11 None Parallel output current
unbalance
36 None
High Inverter voltage 12 None Over temperature 41 None
Low Inverter voltage 13 None CPU communication failure 42 None
Inverter output short
circuited
14
Overload 43
Negative power fault 1A None
3-9. Warning Indicator
Warning
Description
code
Icon (flashing)
Alarm
Battery is not connected
01
Beeping every second
Over charge
07
Beeping every second
Low battery
08
Beeping every second
Overload
09
Beeping twice every second
Fan failure
0A
Beeping every second
EPO enabled
0B
Beeping every second
Over temperature
0D
Beeping every second
Charger failure
0E
Beeping every second
I/P fuse broken
10
Beeping every second
Overload 3 times in 30
minutes
33
Beeping every second
Cover of maintain switch is
open
3A
Beeping every second

Related product manuals