12
Indicates the UPS is charging battery.
Battery information
Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beep
ing
once every
2
minutes
Yes
Battery mode
Beep
ing
once every
4
seconds
Fault mode
Beeping continu
ou
sly
Warning
Overload
B
eep
ing
twice every second
No
Low
b
attery
Beeping once every second
Battery unconnected
Over
c
harge
EPO enable
Fan failure
/Over
temp
erature
Charger failure
IP fuse
broken
Over
l
oad
3
times in 30min
Cover of m
aintain switch is open
Fault
Bus start failure
Beeping continuously
Yes
Bus over
Bus under
Bus unbalance
Inverter soft start failure
High Inverter voltage
Low Inverter voltage
Inverter output short circuited
Negative power fa
ult
Battery SCR short
circuited
Inver
ter
relay short
circuited
Over temperature
CPU communication
failure
Overload
Charger short
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the step
only available for long-run model). Then set the input breaker at “ON” position. At this time the fan is