08: Voltage range for bypass
Interface Setting
Set the acceptable low voltage for bypass.
Setting range is from 110V to 209V and the default value is 176V
09: Voltage range for bypass
Interface Setting
Set the acceptable low voltage for bypass.
Setting range is from 231V to 276V and the default value is 264V
10: Frequency range for bypass
Interface Setting
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
11: Frequency range for bypass
Interface Setting
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
12: Battery voltage calibration
Interface Setting