108 Powerdrive F300 Getting Started Guide
Issue Number: 5
11.8 Listed accessories
11.8.1 Option modules
The following option modules and accessories are UL listed:
Open Type:
11.9 cUL Marking requirements
11.9.1 External transient suppression
Model numbers 07500530, 07500730, 08500860, 08501080 rated 575 V require external
transient suppression in order to comply with cUL approval requirements:
11.9.2 Opening of branch-circuit protection
SI-PROFINET RT SI-I/O
SI-Ethernet SD-Card Adaptor
SI-DeviceNet KI-485 Adaptor
SI-CANopen KI-HOA Keypad RTC
SI-PROFIBUS SMARTCARD
Not all option modules are compatible with all drive models.
NOTE
Transient surge suppression shall be installed on the line side of this equipment and shall
be rated 575 Vac (phase to ground), 575 Vac (phase to phase), suitable for overvoltage
protection category III, and shall provide protection for a rated impulse withstand voltage
peak of 6 kV and a clamping voltage of maximum 2400 V.
The opening of the branch-circuit protective device may be an indication that a fault has
been interrupted. To reduce the risk of fire or electric shock, current-carrying parts, and
other components of the controller should be examined and replaced if damaged.
CAUT ION
WARNING
Powerdrive F300 Getting Started Guide English Iss2.book Page 108 Tuesday, July 28, 2015 3:23 PM