Powerdrive F300 Getting Started Guide 67
Issue Number: 5
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Basic parameters
(Menu 0)
Running the
motor
Optimization
NV Media Card
Operation
Further
information
UL listing
information
7.2 Quick Start / start-up
7.2.1 Open loop
Action Detail
Before
power-up
Ensure:
• The drive enable signal is not given (terminal 29)
• Run signal is not given
• Motor is connected
Power-up the
drive
Verify that Open Loop mode is displayed as the drive powers
up. If the mode is incorrect see section 5.6
Changing the
operating mode
on page 52.
Ensure that the drive displays ‘Inhibit’
Enter motor
nameplate
details
Enter:
• Motor rated frequency in Pr 00.047 (Hz)
• Motor rated current in Pr 00.046 (A)
• Motor rated speed in Pr 00.045 (rpm)
• Motor rated voltage in Pr 00.044 (V) - check if or
connection
Set maximum
frequency
Enter:
• Maximum frequency in Pr 00.002 (Hz)
Set
acceleration /
deceleration
rates
Enter:
• Acceleration rate in Pr 00.003 (s to Pr 1.006)
• Deceleration rate in Pr 00.004 (s to Pr 1.006)
Motor
thermistor
set-up
The motor thermistor can be selected in Pr 07.011. Refer to
Pr 07.011 for further information.
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
VHzmin
-1
kW cos
φ
A
230
400
50 1445 2.20 0.80 8.50
4.90
CN = 14.5Nm
240
415
50 1445 2.20 0.76 8.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,4 6A P=110W R.F 32MN
I.E.C 34 1(87)
Powerdrive F300 Getting Started Guide English Iss2.book Page 67 Tuesday, July 28, 2015 3:23 PM