Powerdrive F300 Getting Started Guide 25
Issue Number: 5
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting started
Basic parameters
(Menu 0)
Running the
motor
Optimization
NV Media Card
Operation
Further
information
UL listing
information
3.6 Terminal size and torque settings
Table 3-1 Drive control and relay terminal data
Table 3-2 Drive power terminal data
Model Connection type Torque setting
All Plug-in terminal block 0.5 N m (0.4 lb ft)
Model size
AC terminals DC terminals Ground terminal
Recommended
3 and 4
Plug-in terminal block T20 Torx (M4)
T20 Torx (M4) /
M4 Nut (7 mm AF)
0.7 N m (0.5 lb ft) 2.0 N m (1.47 Ib ft) 2.0 N m (1.47 Ib ft)
5
Plug-in terminal block
1.8 N m (1.3 lb ft)
T20 Torx (M4) /
M4 Nut (7 mm AF)
M5 Nut (8 mm AF)
1.5 N m (1.1 lb ft) 1.5 N m (1.1 lb ft) 2.0 N m (1.47 Ib ft)
6
M6 Nut (10 mm AF)
6.0 N m (4.42 Ib ft)
7
M8 Nut (13 mm AF)
12.0 N m (8.85 Ib ft)
8 to 11
M10 Nut (17 mm AF)
15 N m (11.1 Ib ft)
Powerdrive F300 Getting Started Guide English Iss2.book Page 25 Tuesday, July 28, 2015 3:23 PM