Figure 5-2: Wiring
A. Minimize distance
B. Trim shield and insulate
C. Ground for transient protection
D. Shield connected to power supply ground
E. Insulate shield
3. Replace the housing cover.
NOTICE
Emerson recommends tightening the cover until there is no
gap between the cover and the housing.
4. Plug and seal unused conduit connections.
5.2
Power supply for a 4-20 mA HART
®
The transmitter operates on 10.5 to 42.4Vdc at the terminal of the
transmitter. The DC power supply should provide power with less
than two percent ripple. Loops with a 250 Ω resistance require a
minimum of 16.6 V.
Note
The transmitter must have a minimum of 250 Ω to communicate
with a communication device. If you are using a single power supply
to power more than one Rosemount 3051 Transmitter, ensure the
power supply used and the circuitry common to the transmitters do
not have more than 20 Ω of impedance at 1200 Hz.