2. Equipment evaluated for atmospheric pressure range between
80 kPa (0.8 bar) to 110 kPa (1.1 bar).
3. The Rosemount 3051 Transmitter with the transient terminal
block (option code T1) will not pass the 500 Vrms dielectric
strength test, and this must be taken into account during
installation.
4. Flame-proof joints are not intended for repair.
9.5.5 E6 Canada Explosion-proof, Dust Ignition-proof, and Division 2
Certificate
1053834
Standards
CAN/CSA C22.2 No. 61010-1-12, CAN/CSA C22.2 No.
94.2-20, CSA C22.2 No. 25-17, CAN/CSA C22.2 No. 30:20,
CAN/CSA C22.2 No. 213-17 +UPD1 (2018) +UPD2 (2019)
+UPD3 (2021), CAN/CSA C22.2 No. 60079-0:19, CAN/CSA
C22.2 No. 60079-1:16, ANSI-ISA-12.27.01–2021
Markings
XP: CL I, DIV 1, GP B, C, D T5
Ex db IIC T5 Gb
Seal not required
DIP: CL II, DIV 1, GP E, F, G; CL III T5;
T5: –50 °C ≤ T
a
≤ +85 °C
NI: CL I DIV 2 GP ABCD T4
T4: -60 °C ≤ Ta ≤ +70 °C;
Single seal - temp limits per 03031-1053
Type 4X, IP 68
Specific Conditions for Use:
1. The Rosemount 3051 Transmitter housing contains aluminum
and is considered a potential risk of ignition by impact or
friction. Care must be taken into account during installation
and use to prevent impact and friction.
2. Equipment evaluated for atmospheric pressure range between
80 kPa (0.8 bar) to 110 kPa (1.1 bar).
3. Flame-proof joints are not intended for repair.
9.6
Europe
9.6.1 E8 ATEX Flame-proof and Dust
ATEX Certificate
KEMA00ATEX2013X (Ex db); Baseefa11ATEX0275X
(Ex ta)
February2024 Quick Start Guide