8.0 Product Certifications
Rev 1.14
8.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can be
found at EmersonProcess.com/Rosemount
.
8.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by a nationally recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
8.3 Installing Equipment in North America
The US National Electrical Code
®
(NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area classification,
gas, and temperature class. This information is clearly defined in the respective
codes.
8.4 USA
E5 US Explosionproof (XP) and Dust Ignition-proof (DIP)
Certificate: 3008216
Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011,
FM Class 3810 – 2005, ANSI/NEMA
®
250 – 2003
Markings: XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(-50 °C ≤ T
a
≤ +85 °C); Factory Sealed; Type 4X
I5 US Intrinsically Safe (IS) and Nonincendive (NI)
Certificate: 3031960
Standards: FM Class 3600 –2011, FM Class 3610 – 2007, FM Class 3611 – 2004,
FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III;
Class 1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D;
T4(-50 °C ≤ T
a
≤ +70 °C); when connected per Rosemount drawing
03151-1206; Type 4X
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using general
Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See drawing 03151-1206.
IE US FISCO Intrinsically Safe
Certificate: 3031960
Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
FM Class 3616 – 2006, FM Class 3810 – 2005, NEMA 250 – 1991
Markings: IS CL I, DIV 1, GP A, B, C, D; T4(-50 °C ≤ T
a
≤ +70 °C); when connected per
Rosemount drawing 03151-1006; Type 4X