Standards:
EN IEC 60079-0: 2018, EN 60079-11: 2012
Markings:
[HART]: II 1 G Ex ia IIC T6…T4 Ga
[Fieldbus/PROFIBUS]: II 1 G Ex ia IIC T4 Ga
See Table 5-5 for entity parameters and temperature classifications.
Special Conditions for Safe Use (X):
1. The equipment must be installed in an enclosure which affords
it a degree of protection of at least IP20 in accordance with the
requirements of IEC 60529. Non-metallic enclosures must have
a surface resistance of less than 1 GΩ; light alloy or zirconium
enclosures must be protected from impact and friction when
installed in a Zone 0 environment.
2. When fitted with the Transient Protector Assembly, the
equipment is not capable of withstanding the 500 V test as
defined in Clause 6.3.13 of EN 60079-11:2012. This must be
taken into account during installation.
5.6.3 N1 ATEX Type n – with enclosure
Certificate:
BAS00ATEX3145
Standards:
EN 60079-0: 2012+A11: 2013, EN 60079-15: 2010
Markings:
II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T
a
≤ +70 °C)
5.6.4 NC ATEX Type n – without enclosure
Certificate:
[Headmount Fieldbus/PROFIBUS
®
, Railmount HART
®
]:
Baseefa13ATEX0093X
[Headmount HART]: Baseefa12ATEX0102U
Standards:
EN IEC 60079-0: 2018, EN 60079-15: 2010
Markings:
[Headmount Fieldbus/PROFIBUS, Railmount HART]: II
3 G Ex nA IIC T5 Gc (–40 °C ≤ T
a
≤ +70 °C)
[Headmount HART]: II 3 G Ex nA IIC T6…T5 Gc; T6(–60
°C ≤ T
a
≤ +40 °C); T5(–60 °C ≤ T
a
≤ +85 °C)
Special Conditions for Safe Use (X):
1. The Rosemount 644 Temperature Transmitter must be
installed in a suitably certified enclosure such that it is
afforded a degree of protection of at least IP54 in accordance
with IEC 60529 and EN 60079-15.