EasyManuals Logo

Emerson Rosemount MultiVariable 3051S Series User Manual

Emerson Rosemount MultiVariable 3051S Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
1 Mount the transmitter
1.1 Liquid flow applications
Procedure
1. Place taps to the side of the line.
2. Mount beside or below the taps.
3. Mount the transmitter so that the drain/vent valves are oriented
upward.
A
A. Direction of flow
1.2 Gas flow applications
Procedure
1. Place taps in the top or side of the line.
2. Mount beside or above the taps.
A
A. Direction of flow
October 2018 Quick Start Guide
Quick Start Guide 3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Rosemount MultiVariable 3051S Series and is the answer not in the manual?

Emerson Rosemount MultiVariable 3051S Series Specifications

General IconGeneral
TypeMultiVariable Transmitter
Accuracy±0.04% of span
Ambient Temperature Limit-40 to 185 °F (-40 to 85 °C)
ApprovalsFM, CSA, ATEX, IECEx
ServiceLiquid, Gas, Steam
Warranty5 years
Process Temperature Range-40 to 257°F (-40 to 125°C)
Response Time100 ms
Power Supply10.5 to 42 V DC
Communication ProtocolsHART, FOUNDATION Fieldbus, PROFIBUS
Housing MaterialAluminum
DisplayOptional LCD
Process Connection1/4" NPT
Electrical Connection1/2–14 NPT, M20 x 1.5
Enclosure RatingNEMA 4X, IP66
Measurement TypesDifferential Pressure, Static Pressure, Temperature