ND ATEX Dust
Certificate
BAS01ATEX1374X
Standards
EN 60079-0:2012, EN 60079-31:2009
Markings
II 1 D Ex ta IIIC T105 °C T
500
95 °C Da, (–20 °C ≤T
a
≤ +85 °C),
V
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of
the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs which
maintain the ingress protection of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for the ambient
temperature range of the apparatus and capable of withstanding a 7J
impact test.
4. The SuperModule(s) must be securely screwed in place to maintain the
ingress protection of the enclosure(s).
N1 ATEX Type n
Certificate
Baseefa08ATEX0065X
Standards
EN 60079-0:2012, EN 60079-15:2010
Markings
II 3 G Ex nA IIC T4 Gc, (–40 °C ≤T
a
≤ 70 °C), V
max
= 45 V
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment is not capable
of withstanding the 500 V electrical strength test as defined in Clause
6.5.1 of EN 60079-15:2010. This must be taken into account during
installation.
10.1.4 International
E7 IECEx Flameproof and Dust
Certificate
IECEx KEM 08.0010X (Flameproof)
Standards
IEC 60079-0:2011, IEC 60079-1:2014,IEC 60079-26:2014
Markings
Ex db IIC T6…T4 Ga/Gb, T6(–60 °C≤ T
a
≤ +70 °C), T5/T4(–60 °C ≤
T
a
≤ +80 °C)
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Quick Start Guide October 2018
36 Rosemount 3051SMV