Specific conditions of use:
1. Cable glands enabling cables to enter the enclosure shall be
ATEX certified as equipment. When installed, the cable gland
must maintain the marked IP rating of the enclosure.
2. End users must follow specific installation and operating
instructions supplied by the manufacturer to prevent
exceeding the heat dissipating limits for the desired
temperature code for an operating ambient and to follow the
information regarding the correct selection of cables and cable
glands.
3. The painted enclosure may present a potential electrostatic
ignition hazard and must not be rubbed or cleaned with a dry
cloth.
4. The maximum input power is restricted to 0.5 W.
9.7.2 ATEX Intrinsic safety
Note
This certification is not yet available. It has been applied for and is
currently in process.
Certificate:
Not yet available
Standard:
EN IEC 60079-0: 2018 and EN 60079-11: 2023
Marking:
II 1 G, Ex ia IIB T4 Ga (ST) and II 1 G, Ex ia IIB T2 Ga (HT)
(–40 °C ≤ T
a
≤ +75 °C)
Specific conditions of use:
TBA
9.8
International
9.8.1 IECEx Flameproof
Certificate:
IECEx SGS 23.0041X
Standard:
IEC 60079-0: 2017 Ed 7.0 and IEC 60079-1: 2014 Ed 7.0
Marking:
Ex db IIB T6…T4 Gb (ST) and Ex db IIB T6…T2 Gb (HT)
(–40 °C ≤ T
a
≤ +75 °C)
Specific conditions of use:
1. Cable glands enabling cables to enter the enclosure shall be
IECEx certified as equipment. When installed, the cable gland
must maintain the marked IP rating of the enclosure.
Quick Start Guide May2024
76 Emerson.com/Rosemount