Page: 14
•In AC mode, press and release the POWER ON/OFF/TEST button for 1 second to perform a self- test�
During the self-test, the UPS momentarily operates in back-up mode (YELLOW LED will illuminate for
10 seconds then will change back to GREEN)� If the UPS passes the self-test, it returns to AC mode�
•In AC mode for 30 Days, the UPS will auto perform a self- test� During the self-test, the UPS momentarily
operates in back-up mode (YELLOW LED will illuminate for 10 seconds then will change back to GREEN)�
If the UPS passes the self-test, it returns to AC mode�
•Additionally, a self-test can be initiated via UPSwatch software or Active Comm Card� Contact
Tech Support for details�
NOTE: The UPS needs to be continuously charged for more than 24 hours, otherwise the battery test will not
be done�
If the self-test results in a failure, the UPS will change to AC mode� The UPS will pass through the input to the
load.Theredandyellowledwillstartflashinginanalternatingpatterntoinformuserthebatteryneedstobe
replaced�
STANDBY MODE
This feature is only available during back-up mode� Standby mode can be executed remotely using the COMM
CARDs� This feature puts the UPS on standby after a maximum of 3 minutes (unless runtime is less than 3
minutes) and auto-recovers once AC power returns� This 3-minute window (or maximum run time depending
on loading) allows the user to shut down their load or place equipment into safe mode�
GREEN MODE
The Green mode is only for 230V models only� By default, Green Mode Enabled� If the load level is less than
approximately 8% ~ 12%, the UPS will shut down to save battery in 3 minutes� If power is restored within 3
minutes the UPS will return to AC mode� Green Mode can be ENABLED or DISABLED by pressing the POWER
ON/OFF at start-up shown on below table�
Green Mode Alarm Signal
Enabled Press Power ON/OFF button and release until "3 beeps"
Disabled Press Power ON/OFF button and release until "2 beeps"
REMOTE ON/OFF
•Allows the user to perform remote power ON/OFF functions using a switch on terminals (non-polarized)
to toggle ON/OFF state�
•To Enable the UPS, close the switch that is connected to the terminals�
•To Disable the UPS, open the switch that is connected to the terminals�