Description
Catalog Number
SDU 500B SDU 850B SDU 500B-5 SDU 850B-5
ENVIRONMENT
Ambient
Operation
0–95% humidity,non-condensing�
Ordinary Location: 0 - 50 °C up to 3000m/ Hazardous Location: 0 - 40 °C up to 2000m
Audible Noise
<40 dBA (1 m from surface)
Vibration
Operating - IEC60068-2-6, Sine Wave: 10Hz to 60 Hz displacement of 0�35mm,
60Hzto500Hz@5G;60minperaxisforallX,Y,Zdirection.
Non-operating-IEC60068-2-6,Random:5Hzto500Hz@2Grms;
20minperaxis for all X,Y,Z
Shock
Operating - IEC60068-2-27, Half Sine Wave: 10G for a duration of 10g
for a duration of 10ms, 3 shocks each in 3 axes in positive and negative direction�
Non-operating - IEC60068-2-27, Half Sine Wave: 20g for duration of 10ms,
3 shocks in 3 axes in positive and negative direction�
WEIGHT & DIMENSIONS
Net Weight
10�8 lb� (4�9kg) 11�5 lb� (5�2kg) 10�8 lb� (4�9kg) 11�5 lb� (5�2kg)
H x W x D
4�89 x 10�91x 5�22in(124�2 x 277�0 x132�7 mm)
CERTIFICATIONS
Safety
UL 1778, 5th Ed�/CSA 107�3 overvoltage category II, pollution
degree 2, evaluated for use in UL 508 industrial control applications
overvoltage category III, pollution degree 3 with no output derating
UL121201/CSA 213 Class I, Division 2 Groups A B C D T4
EN IEC 60079-0, EN IEC 60079-7, EN IEC 60079-15
II 3 G Ex ec nC IIC T4 Gc, UL 20 ATEX 2442X, UL21UKEX2170X
LVD EN 62040-1
ODVA Compliant
EMC
FCC Part 15, Subpart B, Class A Level 4
EMCDirective–EN62040-2;EN55032;EN55011,EN55024,
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN
61326-1, EN61000-3-2, EN 61000-3-3, IEC/EN 61000-4 Series (Level
4, Criterion A), IEC/EN 61000-4-3 (Level 3, Criterion A)