ER5000 — 
152
The ERTune™ Program: Basic Features
A Typical Step Tuning Example
This section is an example of the proper sequence of steps to 
follow, as well as typical settings, for a step tuning session for 
the ER5000.
IMPORTANT
IMPORTANT
The PID settings downloaded during setup provide 
excellent control for most applications. In some cases, minor adjustments 
may be required to optimize performance. Refer to Table 1: Effect of P, 
I and D Increases on Response Curve of Controller in the How It Works 
section for basic tips on adjusting the PID settings.
If, however, you nd that these minor adjustments do not give 
satisfactory results,  zero out the controllers, refer to the Rules of Thumb 
for PID Tuning as well as the detailed Tuning Tips beginning on page 149 
and build your own conguration “from scratch.” You can return to the 
default settings at any time by following the steps To reset the ER5000 to 
its default PID settings.
Tuning is a gradual process, with repeated cycles of changing 
settings and monitoring system response. Most of the steps in 
this example will be repeated multiple times until the desired 
response curve is seen in the Plot Screen.
The Initial Settings
•  Setpoint Source:   ERTune™ Program
•  Type:   Toggle
•  Setpoint 1:   25%
•  Setpoint 2:   75%
•  Proportional:   400
•  Derivative:   0
•  Integral:   0
•  Maximum:   0
•  Minimum:   0
•  Deadband:   0
To activate the Plot Screen
1.  Click the Start Plot Button. 
To toggle the setpoint
1.  Click in the white space below the Setpoint 1 and Setpoint 2 
entry elds. The words Hit Space Bar to Toggle appear.
2.  Press the Space Bar. Each press toggles the setpoint.
(continued next page)