10  Electronic Bypass Controller Installation and Commissioning Guide
2.5 Wiring and Precautions 
2.5.1 General 
1.  DO NOT connect or disconnect wiring or perform signal checks while the power 
supply is turned ON. 
2.  Connect the power supply wiring to the electronic bypass input terminals L1, L2 
and L3 on the main circuit disconnect device.  
3.  Connect the motor wiring to the bypass output terminals T1, T2 and T3 at the 
Class 10 Motor O/L or the output reactor if installed. 
4.  Never touch the output circuit directly or place the output line in contact with the 
package enclosure. 
5.  DO NOT connect power factor correction capacitors on the output circuit. 
6.  Power supply wiring and motor wiring must be in separate conduits with separate 
ground conductors. (DO NOT use conduits as ground). 
7.  Control wiring must be in conduit separate from both power supply and motor 
wiring. 
8.  Tighten the screws on the main circuit disconnect (if provided) and control circuit 
terminals. 
9.  Observe national and local codes when wiring electrical devices. 
Failure to observe these precautions may result in equipment damage or improper 
operation and may not be covered under warranty. 
2.5.2 Input Wiring 
The electronic bypass package may be supplied with several different input device 
options. These input options include protective devices as well as non–protective 
devices. It is the responsibility of the installing parties to ensure that requirements 
for branch circuit protection of the appropriate size and location are observed. All 
incoming power is connected to terminals L1, L2, and L3. The following input options 
are available. 
•  Fused disconnect 
•  Circuit breaker 
•  Input line reactor 
•  Input RFI lter