32 Electronic Bypass Controller Installation and Commissioning Guide
Section 6 - Alarm & Faults
There are two different locations a fault or alarm will be displayed:
1. The electronic bypass keypad
2. The VFD keypad
6.1 Electronic Bypass Keypad Alarms and Faults
There are four (4) Alarm LEDs on the electronic bypass keypad indicating the faults
that may occur. They are as follows:
1. Motor Overload: Indicates that the manual motor overload relay has tripped.
Check that overload relay is properly set for motors full load Ampere rating. Check
for excessive motor current and load.
2. Safety: Indicates that an external safety interlock is in the open position.
If a safety input is not used, check the bypass terminal block for a jumper between
terminals TB2-3 and TB2-8. If a safety input is used, verify that the safety contact
is closed.