Electronic Bypass Controller Installation and Commissioning Guide 31
5.2 Recommended Programming
Following is a list of parameters that should be programmed at the time of start-up.
These values are recommendations only, actual settings should be determined by the
application requirements, conditions, and the policies of the equipment owners. Refer
to the respective drive User Guide for a full parameter list and explanation.
Parameter
Menu 0
Equivalent Description
Setting Units
Fan Pump
01.006 00.011
Max. Speed Hz
60 60 Hz
01.007 00.010
Min Speed Hz
15 6 Hz
02.011 00.012
Acceleration rate 1
100 16.6 s/100 Hz
02.021 00.013
Deceleration rate 1
100 16.6 s/100 Hz
05.007 00.020
Motor rated current
From Motor A
05.008 00.019
Motor load rpm/rated speed
From Motor RPM
05.009 00.018
Motor rated voltage
From Motor V
05.013 00.015
Dynamic V/ F ux optimize select
OFF OFF -
06.009 00.023
Catch a spinning motor
1 1 -
07.019 -
Analog output 1 source
05.001 05.001 menu.param
08.011
Digital I/O 01
1 1 Invert
08.021 -
Digital I/0 01 Source Destination
10.001 10.001 Drive OK
11.044 00.031
Security status
(1) (1) -