Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 18.4 7.0
41 3.5 FLA 8.5
66 5 FLA 11.7
95 8 FLA 18.1
* FLA = Full Load Amps
Table 2.19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 20.5 8.1
41 3.5 FLA 9.6
66 5 FLA 11.7
95 8 FLA
* FLA = Full Load Amps
Table 2.20 Electrical data—High ambient models
(105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 18.0 6.9
41 3.5 FLA 8.4
66 5 FLA 10.9
95 8 FLA
* FLA = Full Load Amps
Table 2.21 Electrical data—Quiet-Line models (95°F/35°C)
50Hz
2.8 Checklist for Completed Installation
1. All items unpacked and checked.
2. Proper clearances for service access maintained around equipment.
3. Equipment is level and mounting fasteners are tight.
4. Piping completed to refrigerant loop.
Vertiv | Liebert PFH Installer/User Guide | 26

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson VERTIV Liebert Mini-Mate2 Series and is the answer not in the manual?

Emerson VERTIV Liebert Mini-Mate2 Series Specifications

General IconGeneral
BrandEmerson
ModelVERTIV Liebert Mini-Mate2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals