Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 18.4 7.0
41 3.5 FLA — 8.5
66 5 FLA — 11.7
95 8 FLA — 18.1
* FLA = Full Load Amps
Table 2.19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 20.5 8.1
41 3.5 FLA — 9.6
66 5 FLA — 11.7
95 8 FLA — —
* FLA = Full Load Amps
Table 2.20 Electrical data—High ambient models
(105°F/41°C) 50Hz
Model #
Nominal
Capacity
Tons
* Electrical
Characteristic
Input Voltage-Phase
220-1 380/415-3
36 3 FLA 18.0 6.9
41 3.5 FLA — 8.4
66 5 FLA — 10.9
95 8 FLA — —
* FLA = Full Load Amps
Table 2.21 Electrical data—Quiet-Line models (95°F/35°C)
50Hz
2.8 Checklist for Completed Installation
1. All items unpacked and checked.
2. Proper clearances for service access maintained around equipment.
3. Equipment is level and mounting fasteners are tight.
4. Piping completed to refrigerant loop.