52 • XM678D I&O Manual 026-1219 Rev 3
idF 6 Defrost interval 0 to 120hours
Sets the time interval between the
beginn
ing of two defrost cycles.
[idF = 0]: t
he defrost can only be
activ
ated manually, or through RS485
or from an external contact or from the
LAN.
MdF 45
(Maximum) defrost
duration
0 to 255mi
n
When dPA is not present, it sets t
he
defrost duration, otherwise it sets the
maximum duration for defrost.
dSd 0
Defrost start delay
after request
0 to 255mi
n
Useful when different de
frost start
times are necessary to avoid
overloading the plant.
dFd it
Display during
defrost
rt
; it; SEt; dEF
rt = real temperature for Lod probe
it =
initial temperature (reading when
defros
t start)
SEt = s
etpoint value
dEF = “dEF” label is v
isualized
dAd 30 Display delay 0 to 255min
Set the maximum time between the end
of defrost and the rest
arting of the real
room temperature display.
Fdt 0
Drain downtime
after defrost
0 to 255
min
Time interval between reaching the
defrost
termination temperature and the
restoration of the control’s normal
operation. This time allows the
evaporator to eliminate water drops that
might have formed due to defrost.
The
fan and the thermoregulation outputs
are OFF during this time.
dPo n
Defrost at power
ON
n; Y
First defrost after startup:
Y = immediately
n = after the idF tim
e
dAF 0.0
Defrost delay after
continuous cycle
0.0 to 24h
00min (144)
Time interval between the end of the
fast freezing cycle
and the following
defrost related to it.
Format: hours.1
0m
in
Resolution: 10min
FAN
FPA P2 Fan probe A
nP(0); P1(1); P2(2);
P3(3); P4(4);
P6(5)
First probe used for fan. If [
FP
A = nP],
the regulation is performed with real
value of FPb.
FnC O-n Fan operating mode C-n; C-Y; O-n; O-Y
C-n = running with the solenoid valve,
OFF du
ring the defrost
C-Y =
running with the solenoid valve,
ON d
uring the defrost
O-n = con
tinuous mode, OFF during
the d
efrost
O-Y =
continuous mode, ON during the
defros
t
Label Value Description Range Notes
Table 24-1 - Default Parameter Map