24 • XM678D I&O Manual 026-1219 Rev 3
14 Multimaster Function Menu (SEC)
The function “section” SEC is enabled when the icon is lit. It allows entering in the remote programming
mode from a keyboard not physically connected to the board through the LAN functionality.
EXAMPLES:
1. To modify the same parameter values in all the
devices connected to the LAN: enter the
multimaster menu. Select and confirm ALL. Exit
from the multimaster menu. Enter the programming
menu and change the required parameter values.
The new values will be changed on all devices
connected to the LAN.
2. To modify a parameter value in the device with
[Adr = 35]: find the relevant indexed section (the
one linked to [Adr = 35]). Enter the multimaster
menu. Select and confirm this section from the
multimaster menu. Exit from the multimaster menu.
Enter the programming menu and change the
required parameter value.
3. If the alarm nod is present: enter the multimaster
menu. Select and confirm the LOC section. Exit
from multimaster menu.
Figure 14-1 - Multimaster Function Menu (SEC)
Action Button or display Notes
Enter menu
Press the up arrow key for about three (3) seconds, the icon will be
ON.
Waiting for action SEC
The menu to change the section will be entered. SEC label will be
displayed.
Enter section list
Press SET to confirm. The following list will be available to select the
proper network function.
Select proper function
or
LOC
ALL
SE1
SEn
SE8
To gain access only to the local device.
To gain access to all the devices connected to the LAN.
To gain access to the device with 1st Adr (*)…
To gain access to the device with 8th Adr (*)
Confirm Select and confirm an entry by pressing SET button.
Exit menu Press SET and up arrow together or wait about 10 seconds.
Table 14-1 - Multimaster Function Menu Action Buttons
(*) The devices on the LAN are indexed by using the Adr parameter (in ascending order).