22 • XM678D I&O Manual 026-1219 Rev 3
12 How to Program
the Parameters
(Pr1 and Pr2)
The device has two programming levels: Pr1 (direct
access) and Pr2 (password-protected, access for
higher level users).
ACCESS to
Pr1
Press for three (3) seconds
to enter the first
programming level (Pr1).
Select item
or
Press the up arrow or
down arrow key to select
the parameter or
submenu.
Show value
Press the SET button.
Modify
or
Press the up arrow or
down arrow key to change
the value.
Confirm
and store
Press SET (the value will
blink for three (3) seconds
and then display the next
parameter).
EXIT
Press to exit the
programming mode, or
wait for 10 seconds to
exit.
12.1.How to Enter Pr2
To enter Pr2 programming menu:
1. Press SET+ down arrow keys for three (3) seconds
to enter Pr1 menu (the first label will display).
2. Press down arrow until the Pr2 label displays and
then press SET.
3. A blinking “PAS” label displays. Wait for a few
seconds.
4. When a blinking “0 - -” displays, enter the password
[321] by pressing the up arrow and down arrow
keys. Press SET to save.
GENERAL STRUCTURE: The first two items, rtC
and EEV, are related to the submenus of the other
parameters.
• Pressing the SET + up arrow keys on the rtC or EEV
submenu returns you to the parameter list.
• Pressing the SET + up arrow keys on the parameter
list exits the screen.
12.2.How to Move a
Parameter From Pr1 to
Pr2 Level and Vice
Versa
Enter the Pr2 level. Select the desired parameter then
press the SET+ down arrow keys. If the LED on the
left-hand side of the screen is ON, it means that the
parameter is present in Pr1 level; if the LED is OFF,
it means that the parameter is not present in Pr1
(Only Pr2).
Table 12-1 - Programming the Parameters (Pr1 and Pr2)
Figure 12-1 - General Structure