58 • XM678D I&O Manual 026-1219 Rev 3
OdC F-C
Compressor and fan
status with do
or
open
no; FAn; CPr; F-C
no = normal; Fan = Fan OFF;
CPr = Comp
ressor OFF;
F_C = both Compressor and Fan OFF
rrd 15
Output restart delay
with door open
0 to 255
min
The outputs stopped by the OdC
parameter can restart after the rrd time.
ENERGY SAVING
ESP P1
Energy saving
probe sel
ection
nP
; P1; P2; P3; P4; P6;
tEr
-
HES 0
Temperature
increasing durin
g
Energy Saving
[-54°F to 54°F]
[-
30.0
°C to 30.0°C]
Sets the increasing value of the setpoint
during the Energy Saving cycle.
PEL nU
Energy saving
activation when
Ligh
t or/a
nd AUX
are switched OFF
nU(0); LIG(1); AUS(2);
LEA(3)
Energy saving enabled when:
LiG: li
ght switched OFF
AUS: AUX switched OFF
LEA: both light and AUX switched
OFF
nU: fu
nction not used
LAN MANAGEMENT
LMd Y
Defrost
Synchr
onization
n; Y
n = th
e section does not send a global
defros
t command.
Y = the section
sends a command to
start defrost to ot
her controllers.
dEM Y
Defrost end
Synchr
onization
n; Y
n = th
e end of the LAN defrosts are
independ
ent.
Y = the end of
the L
AN defrosts are
synchronized.
LSP n
LAN setpoint
Synchr
onization
n; Y
n = the setpoint value is modified only
in the local section.
Y = the section
setp
oint, when
modified, is updated to the same value
on all the other sections.
LdS n
LAN Display
Synchro
nization
(temperature sent
via LAN)
n; Y
n = th
e setpoint value is modified only
in the local section.
Y
= the value displayed by the section is
sent to
all the other sections.
LOF n
LAN ON/OFF
Synchr
onization
n; Y
This parameter indicates if the ON/OFF
com
ma
nd of the section will act also on
all the other sections:
n = th
e ON/OF command
acts only in
the local section.
Y =
the ON/OFF command is sent to all
the o
ther sections.
LLi Y
LAN Light
Synchr
onization
n; Y
This parameter indicates if the light
com
ma
nd of the section will act also on
all the other sections:
n = th
e light command acts only in the
local section.
Y =
the
light command is sent to all the
other sectio
ns.
Label Value Description Range Notes
Table 24-1 - Default Parameter Map