60 • XM678D I&O Manual 026-1219 Rev 3
O3 0 P3 calibration [-12.0°C to 12.0°C]
Allows possible offset of the probe 3 to
adjust.
P4C nP P4 configuration
nP; PtC; ntC; CtC; PtM;
LAN
nP =
not present; PtC = Ptc
; ntC = ntc;
CtC = ntc US; PtM = Pt1000; LAN =
value received from master
O4 0 P4 calibration [-12.0°C to 12.0°C]
Allows possible offset of the probe 4 to
adjust.
P5C 5Vr P5 configuration
nP; PtC; ntC; CtC;
PtM; 420; 5Vr; LAN
nP = not present; PtC =
Ptc; ntC = ntc;
CtC = ntc US; PtM = Pt1000; 420 = 4
to 20mA; 5Vr = 0 to 5V ratiometric;
LAN = value received from master
o5 0 P5 calibration [-12.0°C to 12.0°C]
Allows possible offset of the probe 5 to
adjust.
P6C CtC P6 configuration nP; PtC; ntC; CtC; PtM
nP = not present; PtC =
Ptc; ntC = ntc;
CtC = ntc US; PtM = Pt1000.
o6 0 P6 calibration [-12.0°C to 12.0°C]
Allows possible offset of the probe 6 to
adjust.
SERVICE
CLt - - -
ON/OFF
pe
rcent
age (C.R.O.)
(read only)
Shows the effective cooling time
calcu
lated by XM600 during regulation
(cooling time percentage).
tMd - - -
Time remaining
befo
re the next
defrost acti
vation
(only for interval
defrost)
(read only)
Shows the time before
the next defrost
wh
en interval defrost is selected.
LSn Auto
Number of devices
in the L
AN
1 to 8 (read only)
Shows the number of sections available
in the LAN.
LAn Auto
List of address of
the LAN devices
1 to 247 (read only)
Identifies the device address (1 to
LSn)
inside the local network of multiplexed
cabinet controller.
Adr 1 MODBUS address 1 to 247
Identifies the device address when
connected to a MODBUS compatible
moni
toring system.
br 96 Baud rate 96, 192 Baud rate selection.
rEL 2.5 Firmware release (read only) Microprocessor firmware release.
Ptb - - - Parameter table (read only)
Shows the original code of the
paramet
er map
.
Pr2 - - - Pr2 menu access (read only) Access to the protected parameter list.
Label Value Description Range Notes
Table 24-1 - Default Parameter Map