S1CG/S1HG refrigerant charge tableTable 2
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
S1CG9 CAH09
.25 oz/ft
(23 g/m)
39.5 S1HG9
WLH09/UNH09
.25 oz/ft
(23 g/m)
51.3
S1CG2 CAH12
.25 oz/ft
(23 g/m)
33.75 S1HG2
WLH12/UNH12
.25 oz/ft
(23 g/m)
45.75
S1CG8 CAH24
.64 oz/ft
(59 g/m)
65.25 S1HG8
WLH24/UNH24
.64 oz/ft
(59 g/m)
63.0
S1CG4 CAH24
.64 oz/ft
(59 g/m)
63.0 S1HG4
WLH24/UNH24
.64 oz/ft
(59 g/m)
74.0
S1CG3 CAC36
.64 oz/ft
(59 g/m)
97.5 S1HG9 CAH09
.25 oz/ft
(23 g/m)
51.3
S1CG6 CAC36
.64 oz/ft
(59 g/m)
80.0 S1HG2 CAH12
.25 oz/ft
(23 g/m)
45.75
S1CG9 WLH09/UNH09
.25 oz/ft
(23 g/m)
39.5 S1HG8 CAH24
.64 oz/ft
(59 g/m)
63.0
S1CG2 WLH12/UNH12
.25 oz/ft
(23 g/m)
33.75 S1HG4 CAH24
.64 oz/ft
(59 g/m)
74.0
S1CG8 WLH24/UNH24
.64 oz/ft
(59 g/m)
65.25
S1CG4 WLH24/UNH24
.64 oz/ft
(59 g/m)
63.0
S1CG3 WLC30/UNC30
.64 oz/ft
(59 g/m)
97.5
Refrigerant Processing (continued)
NOTICE – to fi nd charge adjustment
To nd the charge adjustment and system charge for any air handler and tubing 1.
length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Charge + Line Adjustment
Round to the nearest ounce and allow for gauges and hoses.2.