S
in
g
le-Zone,
S2CG/S2H
G
Dual-Zone
I
nstallation,
Op
eration and Maintenance Manual •
Comfort where it counts 16 P/N 240007754, Rev. C [3/19/2010]
S2CG/S2HG refrigerant charge tableTable 3
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
Condenser
Air handler
pairing
Line charge
per foot
Factory
charge
S2CG99 (2) WLHG09
.25 oz/ft
(23 g/m)
44/44 S2HG99 (2) WLHG09
.25 oz/ft
(23 g/m)
44/44
S2CG22 (2) WLHG12
.25 oz/ft
(23 g/m)
39/39 S2HG22 (2) WLHG12
.25 oz/ft
(23 g/m)
39/39
S2CG92 WLHG09+WLHG12
.25 oz/ft
(23 g/m)
44/39 S2HG92 WLHG09+WLHG12
.25 oz/ft
(23 g/m)
44/39
S2CG99 UNHG09
.25 oz/ft
(23 g/m)
44/44 S2HG99 UNHG09
.25 oz/ft
(23 g/m)
44/44
S2CG22 UNHG12
.25 oz/ft
(23 g/m)
39/39 S2HG22 UNHG12
.25 oz/ft
(23 g/m)
39/39
S2CG92 UNHG09+UNHG12
.25 oz/ft
(23 g/m)
40/39
S2HG92 UNHG09+UNHG12
.25 oz/ft
(23 g/m)
44/39
NOTICE – to fi nd charge adjustment
To  nd the charge adjustment and system charge for any air handler and tubing 1.
length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Charge + Line Adjustment
Round to the nearest ounce and allow for gauges and hoses.2.
Refrigerant Processing (continued)