8. GUEST SCREENS
8.2.1 Room temperature set
The following values identify the daily schedule of the
room temperature Set.
This schedule is divided into two time ranges,
Comfort and Attenuation:
- at 0:00 it starts with Attenuation,
- at the Comfort start time changes to Comfort,
- at the Attenuation start time returns to Attenuation.
The Room temperature Set then assumes the following values:
- in the Comfort range Comfort Temperature,
- in the Attenuation range Attenuation Temperature,
where:
- in heating → Attenuation Temperature
= Comfort Temperature - Attenuation Variation
- in cooling → Attenuation Temperature
= Comfort Temperature + Attenuation Variation
Temp. of
Comfort
Set temp.
environment
Variation in
Attenuation
Room temperature set in heating
Time of Attenuation
Comfort time
Set temp.
environment
Room temperature set in cooling
Temp. di
Comfort
Comfort time
Time of Attenuation
Variation in
Attenuation
The Room Widget displays the Room Temperature Set and the room operating condition
Temperature set
room
Room operating condition
Active Comfort range,
Room temperature set = Comfort Temperature.
Attenuation range active.
Temperature set
room = Attenuation Temperature
Out of house manual
Out of house from presence
contact.
→ Open window contact, Thermostat
(
or ) and Humidistat ( ) consents are inhibited
NOTE:
Thermostat consent involves switching
of the respective relay on board the Febos-Crono.
The thermostat consent is activated when:
in heating → Room temperature
< Room Temp Set - Room Temp Differential
in cooling → Room temperature
> Room Temp Set + Room Temp Differential
GUEST