8. GUEST SCREENS
8.2.2 Relative humidity/dew point SET
The following value identifies the room humidity set point.
As a reference for the Room humidity set pointit is possible to
use:
the Relative humidity→ setting a value between 30 % and 99
%
the Dew temperature → setting a value between 10.0°C and
29.9°C:
The consent of the Humidistat is based on the reference used
when:
• Relative humidity > Room humidity Set point (RH %) + Room
humidity differential (RH %)
• Dew Temperature > Dew temp set point (°C) + Dew temp
differential (°C).
NOTE:
The humidistat consent involves switching
of the respective relay on board the Febos-Crono.
8.2.3 Screenshot 2.2 SLAVE ENVIRONMENT SET
In case you have configured a Modbus network (Master + Slave), on
the Febos-Crono Master there is an additional screen, the 2.2 SET
ENVIRONMENT, in which the operating status of all Febos-Crono
Slave is displayed.
On screen 2.1, press the icon "
" to access the 2.2.
Febos-Crono connected
Not connected
Adress SLAVE Name SLAVE
central
Indipendent
GUEST